Nonfire S104

 
Tikkurila Industry 9L
描述 A waterborne one component intumescent coating. When subjected to heat it expands and forms an insulating layer of foam.
产品特性 Used as a fire retardant paint on interior steel structures. Recommended to be applied on-site during dry conditions. Components painted in workshops must be topcoated before taken outdoors.
推荐用途 Steel structures.

技术参数
特性 Fulfils requirements R15 - R60 (NT FIRE 021), F30 - F60 (DIN 4102). Properties and dimensioning requirements are described in the certified product declaration, TRY-95-2005, published by Teräsrakenneyhdistys ry. (The Finnish Constructional Steelwork Association). The product is approved in Sweden by SITAC (Nr. 0170/05).
色彩类别 White.
光泽组别 哑光
涂布率

Amount

Recommended film thicknesses

Theoretical coverage

 

g/m2

dry

wet

l/m2

m2/l

850

410 µm

670 µm

0.67

1.50

1100

540 µm

870 µm

0.87

1.20

1850

900 µm

1460 µm

1.46

0.70

2650

1290 µm

2090 µm

2.09

0.50

4000

1950 µm

3150 µm

3.15

0.30

4900

2390 µm

3860 µm

3.86

0.25


Practical coverage depends on the application method, painting conditions and the shape and roughness of the surface to be coated.
稀释剂
涂刷方法 Application by brush, roller or airless spray
干燥时间

DFT 400 µm

+23 ºC, RH 50%

Dust dry, after

2 h

Touch dry, after

5 h

Recoatable, after

By itself 4 - 16 h, overtime may cause blistering

Recoatable, after

With LUJA, FONTECRYL 50 and FONTEX AC 45

 4 - 16 h, overtime may cause blistering

Recoatable, after

With TEMACRYL AR 50 and TEMALAC AB 70 4 h


Drying and recoating times are related to the film thickness, temperature, the relative humidity of the air and ventilation.
Solids volume 62 ± 2 volume % (ISO 3233)
66 ± 2 weight %
密度 1,27 kg/l
储存 About one year in dry and cool conditions.
产品编号 009 9003

使用说明
施工条件 All surfaces must be dry. The temperature of the ambient air, surface or paint should not fall below +10 ºC during application and drying. Relative humidity should not exceed 70 %. The surface temperature of the steel should remain at least 3 ºC above the dew point.
准备 Primed surfaces: Oil, grease, salt and dirt are removed from the surface by appropriate means. Repair any damage to the primer coat. Note the overcoating time of primer. (ISO 12944-4)

Note: An approved intumescent coating system always requires a primer coat.
涂刷底漆 TEMAPRIME EUR (40 µm), TEMAPRIME EE (40 µm), TEMACOAT GPL-S PRIMER (60 µm) and FONTECRYL 10 (40 µm).
喷面漆 LUJA, FONTECRYL 50, FONTEX AC 45, TEMALAC AB 70 and TEMACRYL AR 50 about 50 µm (corrosivity category C1).

Before overcoating should the dry film thickness of the coating be controlled with a reliable test method in accordance with SFS 3644/ISO 2808 and a record should be drawn.
涂刷 Application by brush, roller or airless spray. Mix the paint thoroughly before use. Recommended dry film thickness is approximately 400 - 600 µm/layer. At spray application should be used a spray unit with an output of minimum 7 l/min and a pressure ratio of min. 1:45. Diameter of the paint hoses should be at least 3/8", the length should not exceed 15 m. Handle filter 0.31 mm (white), other filters should be removed. Nozzle tip size 0.015" - 0.021", turnable nozzle is recommended. Nozzle shall be chosen according to the efficiency and output of the equipment. Spray angle shall be chosen according to the shape of the object. To improve spraying properties the paint can be heated up to max 40 ºC. If necessary, thin 0 - 5 % with water.
固化 Components painted in work shop should be covered with a plastic film during transport and storage and packed in order to avoid impresses. During winter season in temperature + 20 ºC painted components may not be taken outdoors before 48 hours. Damages shall be repaired immediately in the same way as originally.
工具清洗 Water or FONTECLEAN 1921.
EU VOC 2004/42/EC-限值 The Volatile Organic Compounds amount to < 15 g/litre of paint.

健康安全等级
Containers are provided with safety labels, which should be observed. Further information about hazardous influences and protection are detailed in individual health and safety data sheets. A health and safety data sheet is available on request from Tikkurila Oy. For professional use only.
 
-